(a) The owner, operator, or permittee of a volatile liquid storage tank located in the Port of Anchorage that has a volume of 9,000 barrels (378,000 gallons) or more shall reduce organic vapors emitted to the atmosphere by using
(1) an internal floating roof installed before June 1, 1992;
(2) an internal floating roof that meets the specifications of 40 C.F.R. 60.112b(a)(1), adopted by reference in 18 AAC 50.040;
(3) a closed vent system and control device that collects and reduces organic vapors emitted to the atmosphere by at least 95 percent (six-hour average), as specified in the department's Air Quality Compliance Certification Procedures for Volatile Liquid Storage Tanks, Delivery Tanks, and Loading Racks, adopted by reference in 18 AAC 50.030; or
(4) a system that the department determines is as effective as those described in (2) or (3) of this subsection, using procedures in the document referred to in (3) of this subsection.
(b) The owner, operator, or permittee of a volatile liquid storage tank with an internal floating roof described in (a)(1) of this section shall reduce organic vapors emitted to the atmosphere by modifying the seals and fittings to meet the specifications of 40 C.F.R. 60.112b(a)(1), adopted by reference in 18 AAC 50.040, no later than the first time after June 1, 1995 that the tank is emptied and degassed.
(c) The owner, operator, or permittee of a volatile liquid storage tank that is located in the Port of Anchorage, that has a volume equal to or greater than 952 barrels (40,000 gallons) but less than 9,000 barrels (378,000 gallons), and that is not equipped with a control device described in (a)(1) - (4) of this section, shall, no later than the first time on or after June 1, 1995 that the tank is emptied and degassed, reduce organic vapors emitted to the atmosphere by installing conservation vents on the tank as specified in the document referred to in (a)(3) of this section.
(d) When conducting source testing, the department will, and the owner, operator, or permittee shall, use the procedures specified in the document referred to in (a)(3) of this section to determine compliance with this section. In accordance with those procedures, the owner, operator, or permittee of a volatile liquid storage tank subject to this section shall
(1) periodically inspect air pollution control equipment;
(2) repair any deficiencies detected;
(3) report to the department the results of all inspections and repairs; and
(4) keep records of those inspections and repairs for at least five years.
History: Eff. 1/18/97, Register 141
Authority: AS 46.03.020
Sec. 30, ch. 74, SLA
1993
Editor's note: A complete description of the Port of Anchorage is in the state air quality control plan adopted by reference in 18 AAC 50.030.
Note to HTML Version:
The Alaska Administrative Code was automatically converted to HTML from a plain text format. Every effort has been made to ensure its accuracy, but neither Touch N' Go Systems nor the Law Offices of James B. Gottstein can be held responsible for any possible errors. This version of the Alaska Administrative Code is current through June, 2006.
If it is critical that the precise terms of the Alaska Administrative Code be known, it is recommended that more formal sources be consulted. Recent editions of the Alaska Administrative Journal may be obtained from the Alaska Lieutenant Governor's Office on the world wide web. If any errors are found, please e-mail Touch N' Go systems at E-mail. We hope you find this information useful. Copyright 2006. Touch N' Go Systems, Inc. All Rights Reserved.
Last modified 7/05/2006