(a) Notwithstanding 29 C.F.R. 1910.269(l)(2), as amended, an employer may not allow an employee to approach or take any conductive object, without an approved insulating handle that meets the requirements of 29 C.F.R. 1910.269(j)(1), closer to exposed energized parts of 5,000 volts or greater from phase-to-phase or phase-to-ground than shown in Tables R-6 - R-10 in 29 C.F.R. 1910.269, as amended.
(b) Notwithstanding 29 C.F.R. 1910.269(l)(2) and (l)(3), as amended, an employer may not allow an employee to perform rubber glove work on energized lines of 5,000 volts or greater from phase-to-phase or phase-to-ground.
(c) Notwithstanding 29 C.F.R. 1910.269(l)(2) and (q)(3), as amended, live-line bare-hand work on overhead lines by employees is prohibited.
History: Eff. 12/6/95, Register 136
Authority: AS 18.60.020
Note to HTML Version:
The Alaska Administrative Code was automatically converted to HTML from a plain text format. Every effort has been made to ensure its accuracy, but neither Touch N' Go Systems nor the Law Offices of James B. Gottstein can be held responsible for any possible errors. This version of the Alaska Administrative Code is current through June, 2006.
If it is critical that the precise terms of the Alaska Administrative Code be known, it is recommended that more formal sources be consulted. Recent editions of the Alaska Administrative Journal may be obtained from the Alaska Lieutenant Governor's Office on the world wide web. If any errors are found, please e-mail Touch N' Go systems at E-mail. We hope you find this information useful. Copyright 2006. Touch N' Go Systems, Inc. All Rights Reserved.
Last modified 7/05/2006